Fleet Sizer

HYP V12 1MW · Natural gas genset

Size your fleet

Each 40′ container holds two HYP-TWELVE engines. Tell us how much power you need, from 1 to 100 MW. We’ll show how many containers it takes and the gas to run them.

Primary power with a varying load.

10
MW needed10 containers · Prime rating

Each tile is one 40′ container. Every row of 10 is about 10 MW.

Power delivered

10.60MW delivered
Containers
10
Electrical output
10,600 kWe
Apparent power at 0.8 PF
13,250 kVA
Per container
1,060 kWe
Energy per day (24 h)
254.4 MWh
Voltage
480 V, 3-phase, 60 Hz

Containers are whole units, so delivered power rounds up past your target. Output measured at the generator terminals.

Gas volume

2,020SCFM
Per hour
121,200 SCFH
Per day (24 h)
2,909 MCF/d
Per year (8,760 h)
1,061,712 MCF
Heat input (LHV)
110.0 MMBTU/h

Rated fuel consumption at full load, ISO reference conditions, 100% natural gas.

Gas pressure

2 psig60 psig
Ask your gas utility what it can deliver at the meter.
~10psig at your containers

Within the 5 to 50 psig the containers need.

Required at each container
5 to 50 psig
Connection
10 × 2″ Class 150
Supply line must carry
2,020 SCFM
After internal regulator
0.29 to 1.02 psig
Fuel quality
MN ≥ 80, ~990 BTU/scf

Pressure drops along the supply line, so the farthest container sees less than what leaves your meter.

Gas supply line

2″3″4″6″8″10″12″
Matched to your fleet. Move it to try your existing line.
100 ft1,500 ft
From your gas meter to the farthest container.
8″recommended
Recommended main header
8″ steel
Branch to each container
10 × 2″
Isolation valves
One per branch
This line can feed your fleet

An 8″ line at 10 psig over 500 ft can feed about 12 containers. You need 10.

Planning estimate for a steel line before fittings and valves. Every site is different; final sizing is done by a licensed engineer.

Ready to plan your site?Our team will confirm sizing for your load profile, gas supply and site conditions.

Talk to our team

Planning estimates only, not a quote or performance guarantee. Based on the HYP V12 1MW specification (September 2026). Per-container ratings on natural gas: Standby 1,240 kWe and Prime 1,060 kWe. Reference conditions DIN ISO 3046-1 (14.5 psi, 77°F, 30% RH). Altitude, ambient temperature and fuel quality will reduce output. Fuel consumption tolerance +5%.